5.5 : Thermal Distribution Systems




5.5.4 Thermal Distribution Equipment Design Load and Electricity Intensities, by System Type
Design Load Intensity (W/SF) End Use Intensity (kWh/SF)
Central VAV Central CAV Packaged CAV Central VAV Central CAV Packaged CAV
Condenser Fan 0.3 0.2
Cooling Tower Fan 0.2 0.2 0.1 0.2 0.0
Condenser Water Pump 0.2 0.2 0.3 0.3 0.0
Chilled Water Pump 0.2 0.2 0.1 0.2 0.0
Supply & Return Fans 0.7 0.5 0.6 1.2 1.9 1.9
Chiller/Compressor 1.9 1.8 3.3 1.7 2.3 4.0