3.9 : Educational Facilities




3.9.9 Energy Benchmarks for Existing Primary Schools, by Selected City and End-Use
(thousand Btu per square foot)
IECC Heating Cooling Water Heating Ventilation
Climate Zone Post Pre Post Pre Post Pre Post Pre
Miami 1A 0.7 0.7 20.6 22.4 1.4 1.4 3.1 3.4
Houston 2A 6.4 8.3 13.3 17.2 1.7 1.7 2.4 2.9
Phoenix 2B 4.1 6.1 14.2 19.6 1.6 1.5 2.9 3.6
Atlanta 3A 12.5 16.8 7.6 10.6 2.0 2.0 2.1 2.7
Los Angeles 3B 4.4 4.4 6.1 6.6 1.9 1.9 2.2 2.4
Las Vegas 3B 6.6 10.2 10.1 14.5 1.8 1.7 2.6 3.4
San Francisco 3C 10.9 12.6 2.3 3.0 2.2 2.1 1.9 2.2
Baltimore 4A 18.6 29.8 5.4 7.8 2.2 2.2 1.8 2.5
Albuquerque 4B 13.3 19.5 4.7 6.8 2.2 2.1 2.3 3.1
Seattle 4C 17.0 25.8 1.4 2.0 2.3 2.3 1.5 2.0
Chicago 5A 27.0 33.3 3.9 4.5 2.4 2.4 1.9 2.1
Boulder 5B 18.2 24.1 2.7 3.4 2.4 2.3 1.8 2.2
Minneapolis 6A 34.8 43.2 2.9 3.5 2.6 2.5 1.7 2.0
Helena 6B 28.0 33.5 1.6 1.9 2.6 2.5 1.7 1.9
Duluth 7 42.3 51.8 1.2 1.3 2.9 2.8 1.5 1.9
Fairbanks 8 84.2 99.3 0.7 0.8 3.2 3.1 2.0 2.2
Note(s): Commercial building energy benchmarks are based off of the current stock of commercial buildings and reflect 2004 ASHRAE 90.1 Climate Zones. They are designed to provide a consistent baseline to compare building performance in energy-use simulations. 'Post' refers to buildings construction in or after 1980. 'Pre' refers to buildings construction before 1980. The benchmark building had 73,932 square feet and 1 floor. Benchmark interior lighting energy = 23.72 thousand Btu/SF. Interior equipment energy consumption = 18.77 thousand Btu/SF.