3.9 : Educational Facilities




3.9.12 Energy Benchmarks for Newly Constructed Secondary Schools, by Selected City and End-Use
(thousand Btu per square foot)
IECC Climate Zone Heating Cooling Water Heating Ventilation
Miami 1A 0.7 54.0 1.1 5.5
Houston 2A 8.1 41.0 1.4 5.2
Phoenix 2B 5.8 44.4 1.3 5.6
Atlanta 3A 15.3 25.3 1.7 4.9
Los Angeles 3B 4.1 15.9 1.6 4.7
Las Vegas 3B 8.6 28.2 1.5 5.2
San Francisco 3C 13.9 9.6 1.8 4.7
Baltimore 4A 27.5 20.9 1.9 4.9
Albuquerque 4B 17.9 13.8 1.9 5.1
Seattle 4C 25.8 5.9 2.0 4.5
Chicago 5A 36.7 15.9 2.1 4.9
Boulder 5B 26.3 9.5 2.1 4.9
Minneapolis 6A 50.4 13.4 2.3 5.0
Helena 6B 40.4 6.0 2.3 5.0
Duluth 7 61.0 6.1 2.5 5.3
Fairbanks 8 96.7 2.2 2.8 5.5
Note(s): Commercial building energy benchmarks are based off of the current stock of commercial buildings and reflect 2004 ASHRAE 90.1 Climate Zones. They are designed to provide a consistent baseline to compare building performance in energy-use simulations.The benchmark building had 210,810 square feet and 2 floors. Benchmark interior lighting energy = 15.20 thousand Btu/SF. Interior equipment energy consumption = 11.83 thousand Btu/SF.