3.9 : Educational Facilities




3.9.10 Energy Benchmarks for Newly Constructed Primary Schools, by Selected City and End-Use
(thousand Btu per square foot)
IECC Climate Zone Heating Cooling Water Heating Ventilation
Miami 1A 0.3 15.9 1.4 2.7
Houston 2A 4.7 11.5 1.7 2.2
Phoenix 2B 3.3 12.4 1.5 2.5
Atlanta 3A 8.3 6.2 2.0 1.8
Los Angeles 3B 2.0 3.6 1.9 1.5
Las Vegas 3B 4.7 8.5 1.7 2.2
San Francisco 3C 8.8 2.0 2.1 1.7
Baltimore 4A 15.8 5.0 2.2 1.7
Albuquerque 4B 10.3 4.2 2.1 2.0
Seattle 4C 12.9 1.1 2.3 1.3
Chicago 5A 21.4 3.6 2.4 1.7
Boulder 5B 15.2 2.6 2.3 1.6
Minneapolis 6A 30.9 2.9 2.5 1.7
Helena 6B 24.0 1.5 2.5 1.4
Duluth 7 37.0 1.2 2.8 1.5
Fairbanks 8 59.6 0.5 3.1 1.4
Note(s): Commercial building energy benchmarks are based off of the current stock of commercial buildings and reflect 2004 ASHRAE 90.1 Climate Zones. They are designed to provide a consistent baseline to compare building performance in energy-use simulations.The benchmark building had 73,932 square feet and 1 floor. Benchmark interior lighting energy = 15.80 thousand Btu/SF. Interior equipment energy consumption = 18.77 thousand Btu/SF.