3.8 : Hospitals and Medical Facilities
| 3.8.5 |
Energy
Benchmarks for Existing Outpatient Buildings, by Selected City and End-Use |
|
|
|
|
|
(thousand Btu per square foot) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IECC |
|
|
Heating |
|
Cooling |
|
Water Heating |
|
Ventilation |
|
|
|
Climate Zone |
|
Post |
Pre |
|
Post |
Pre |
|
Post |
Pre |
|
Post |
Pre |
|
| Miami |
|
|
1A |
|
|
65.4 |
60.3 |
|
69.6 |
61.9 |
|
0.7 |
0.7 |
|
24.6 |
23.9 |
|
| Houston |
|
|
2A |
|
|
73.2 |
76.2 |
|
54.0 |
52.9 |
|
0.8 |
0.8 |
|
22.1 |
24.0 |
|
| Phoenix |
|
|
2B |
|
|
79.1 |
79.8 |
|
54.7 |
52.9 |
|
0.7 |
0.7 |
|
23.8 |
25.3 |
|
| Atlanta |
|
|
3A |
|
|
83.1 |
91.1 |
|
41.8 |
42.1 |
|
0.9 |
0.9 |
|
22.1 |
24.6 |
|
| Los Angeles |
|
3B |
|
|
87.8 |
86.3 |
|
37.4 |
35.6 |
|
0.9 |
0.9 |
|
22.5 |
23.1 |
|
| Las Vegas |
|
3B |
|
|
76.6 |
80.5 |
|
44.1 |
44.0 |
|
0.8 |
0.8 |
|
23.2 |
25.5 |
|
| San Francisco |
|
3C |
|
|
85.0 |
93.4 |
|
25.0 |
24.7 |
|
1.0 |
1.0 |
|
20.3 |
22.2 |
|
| Baltimore |
|
4A |
|
|
85.9 |
97.6 |
|
34.8 |
35.3 |
|
1.0 |
1.0 |
|
21.0 |
23.5 |
|
| Albuquerque |
|
4B |
|
|
76.5 |
83.6 |
|
30.4 |
30.9 |
|
1.0 |
1.0 |
|
24.1 |
26.4 |
|
| Seattle |
|
|
4C |
|
|
91.7 |
103.1 |
|
22.8 |
22.6 |
|
1.1 |
1.0 |
|
20.9 |
22.9 |
|
| Chicago |
|
|
5A |
|
|
92.4 |
96.0 |
|
28.1 |
26.4 |
|
1.1 |
1.1 |
|
21.2 |
22.1 |
|
| Boulder |
|
|
5B |
|
|
79.9 |
82.9 |
|
24.7 |
23.3 |
|
1.1 |
1.1 |
|
23.4 |
24.4 |
|
| Minneapolis |
|
6A |
|
|
97.1 |
102.0 |
|
24.9 |
23.5 |
|
1.2 |
1.1 |
|
21.1 |
22.1 |
|
| Helena |
|
|
6B |
|
|
88.6 |
93.2 |
|
19.9 |
18.8 |
|
1.2 |
1.2 |
|
22.3 |
23.3 |
|
| Duluth |
|
|
7 |
|
|
100.6 |
104.6 |
|
17.0 |
15.5 |
|
1.3 |
1.3 |
|
20.8 |
21.2 |
|
| Fairbanks |
|
8 |
|
|
129.2 |
132.6 |
|
12.2 |
10.8 |
|
1.5 |
1.4 |
|
20.6 |
20.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Note(s): |
Commercial
building energy benchmarks are based off of the current stock of commercial
buildings and reflect 2004 ASHRAE 90.1 Climate Zones. They are designed to
provide a consistent baseline to compare building performance in energy-use
simulations. 'Post' refers to buildings construction in or after 1980. 'Pre'
refers to buildings construction before 1980. The benchmark building had
40,932 square feet and 3 floors. Benchmark interior lighting energy = 18.42
thousand Btu/SF. Interior equipment energy consumption = 46.01 thousand
Btu/SF. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|