3.7 : Retail Markets and Companies




3.7.6 Energy Benchmarks for Newly Constructed Retail Buildings, by Selected City and End-Use
(thousand Btu per square foot)
IECC Climate Zone Heating Cooling Ventilation
Miami 1A 0.2 17.0 11.2
Houston 2A 8.1 11.9 10.7
Phoenix 2B 6.4 13.1 10.2
Atlanta 3A 15.3 5.8 9.6
Los Angeles 3B 4.3 1.8 8.0
Las Vegas 3B 11.0 7.5 7.8
San Francisco 3C 16.1 0.4 4.3
Baltimore 4A 28.4 4.3 9.1
Albuquerque 4B 20.2 3.5 8.5
Seattle 4C 28.8 0.6 7.0
Chicago 5A 39.8 2.9 8.9
Boulder 5B 29.7 2.0 8.4
Minneapolis 6A 52.3 2.4 9.0
Helena 6B 45.2 1.1 8.4
Duluth 7 68.9 0.6 5.6
Fairbanks 8 108.9 0.1 9.4
Note(s): Commercial building energy benchmarks are based off of the current stock of commercial buildings and reflect 2004 ASHRAE 90.1 Climate Zones. They are designed to provide a consistent baseline to compare building performance in energy-use simulations. The benchmark building had 24,683 square feet and 1 floor. Benchmark interior lighting energy = 19.2 thousand Btu/SF. Interior equipment energy consumption = 7.63 thousand Btu/SF.